CyberPower LCD HSTP3T40KE uninterruptible power supply (UPS) Double-conversion (Online) 40 kVA 36000 W

SKU
HSTP3T40KE
Login for pricing
In Stock - Available On Backorder
40000 VA, 36000 W, 55 A, LCD, L-N / L-L, 1x Terminal Block, IP20, 250 x 770 x 836 mm, 61 kg
CyberPower LCD HSTP3T40KE uninterruptible power supply (UPS) Double-conversion (Online) 40 kVA 36000 W is available to buy in increments of 1
  • Three-phase Design
  • ECO Mode
  • Dual Inputs
  • Pure Sine Wave Output
  • Maintenance Bypass Switch
  • Emergency Power Off (EPO) Port
  • PowerPanel Management Software
  • Online (Double Conversion) UPS Topology
  • UPS Parallel Expansion
  • Generator Compatible
  • Overload Protection
  • LCD Status Display
  • SNMP/HTTP Remote Management Capability (Optional)
More Information
SKU HSTP3T40KE
EAN 4712856279023
Manufacturer CyberPower
Availability N
Product Family LCD
PDF URLs View PDF
View PDF
CyberPower HSTP3T40KE 3-Phase online UPS provides long-lasting power backup for data closets, transportation and infrastructure, and emergency systems. With parallel expansion capability, the HSTP3T (3-Phase) Series UPS is ideal for critical applications in server rooms, data centers, industrial factories, and power generation plants that require high capacity, high reliability, and extended runtimes.

With integrated IGBT technology and intelligent DSP-based control, the UPS produces less input total harmonic distortion (THDi) and achieves higher power efficiency up to 98% in Economy Mode, making it the most efficient UPS in the industry. Higher operating efficiency equates to lowered BTU heat dissipation and lowered idle power consumption, resulting in an operating expense reduction and a lower carbon footprint.

To improve operating efficiency, the UPS system works in bypass mode under normal conditions, during which the inverter is kept on standby. During power failures, the UPS switches to battery mode and supplies backup power to the connected critical load.
Power
Output voltage regulation1%
Output power factor0.9
Input power factor0.99
Output power36000 W
Input operation voltage (min)132 V
Input operation voltage (max)478 V
Output operation voltage (min)220 V
Output operation voltage (max)415 V
Maximum current42 A
Efficiency96%
Emergency Power Off (EPO)Yes
Output voltage Total Harmonic Distortion (THD)5.5%
Crest factor3:1
Output power capacity40 kVA
Efficiency (Battery mode)96%
Total Harmonic Distortion (THD) (linear load)1%
Total Harmonic Distortion (THD) (non-linear load)5.5%
Power Factor Correction (PFC) typeActive
Efficiency (ECO mode)98%
ECO modeYes
Ports & interfaces
Socket circuit breakerYes
Emergency Power Off (EPO) connectorYes
Serial interfaceYes
Serial interface typeRS-232, RS-485
Performance
Audible alarm modesAlarm when on battery, Battery replacement, Fault, Low battery alarm, Overload alarm
UPS topologyDouble-conversion (Online)
WaveformPure sine
Number of output phases3
Number of input phases3
LED indicatorsYes
EMI/RFI noise filteringYes
Surge protectionYes
Power protection featuresOverload
Noise level58 dB
Audible alarm(s)Yes
Transfer time (Line Mode to Battery Mode)0 ms
Features
Output frequency50/60 Hz
Audible alarm modesAlarm when on battery, Battery replacement, Fault, Low battery alarm, Overload alarm
UPS topologyDouble-conversion (Online)
WaveformPure sine
Output voltage regulation1%
Number of output phases3
Number of input phases3
Output power factor0.9
Input power factor0.99
Output power36000 W
Input operation voltage (min)132 V
Input operation voltage (max)478 V
Output operation voltage (min)220 V
Output operation voltage (max)415 V
Maximum current42 A
Efficiency96%
EMI/RFI noise filteringYes
Surge protectionYes
Emergency Power Off (EPO)Yes
Power protection featuresOverload
Output voltage Total Harmonic Distortion (THD)5.5%
Noise level58 dB
Crest factor3:1
Audible alarm(s)Yes
Output power capacity40 kVA
Efficiency (Battery mode)96%
Total Harmonic Distortion (THD) (linear load)1%
Total Harmonic Distortion (THD) (non-linear load)5.5%
Power Factor Correction (PFC) typeActive
Socket circuit breakerYes
Transfer time (Line Mode to Battery Mode)0 ms
Efficiency (ECO mode)98%
ECO modeYes
Input frequency40/70 Hz
Battery
Number of batteries supported40
Battery voltage12 V
Battery technologySealed Lead Acid (VRLA)
Rechargeable batteryYes
Design
International Protection (IP) codeIP20
Form factorTower
LED indicatorsYes
Product colourBlack
CertificationCE, IEC62040-1, IEC62040-2
Housing materialMetal
Control typeButtons
Display typeLCD
Operational conditions
Operating temperature (T-T)0 - 40 °C
Storage temperature (T-T)-40 - 70 °C
Operating relative humidity (H-H)0 - 95%
Storage relative humidity (H-H)0 - 95%
Operating altitude0 - 1000 m
Technical details
Output frequency50/60 Hz
BypassAutomatic Manual
Certificates
CertificationCE, IEC62040-1, IEC62040-2
Packaging content
ManualYes
Batteries includedYes
Weight & dimensions
Package width400 mm
Package depth960 mm
Package height1050 mm
Weight61 kg
Width250 mm
Package weight75 kg
Height836 mm
Depth770 mm
Packaging data
ManualYes
Package width400 mm
Package depth960 mm
Package height1050 mm
Package weight75 kg
Other features
Overload protectionYes
BypassAutomatic Manual
Search engine powered by ElasticSuite